Power rating |
180 kVA (415/240V WYE) |
Input |
Connection type |
3 phase+neutral+protective conductor (protective ground) (two power strip terminals 70-185 mm2 for each connection) |
Voltage and current rating |
173-415/100-240V WYE (3 phase+neutral+protective conductor (protective ground)), 3 phases х 250A |
Frequency |
50/60 Hz ± 5% |
Grounding control |
Indication of grounding presence/absence |
Output |
Number of connections |
90 connections, 30 managed channels (3 connections per channel) |
Connector type |
Spring loaded clamp terminals: 4 mm2 (6 mm2 without ferrule) for phase and neutral conductors, 2.5 mm2 (4 mm2 without ferrule) for protective ground conductors |
Voltage and current rating of the managed channel |
100-240V (phase+neutral+protective conductor), 25A per each managed channel |
Overcurrent and Short Circuit Protection Parameters |
- Overload protection: configurable 0.1-25А (default setting 25A)
- Short circuit protection: 3 x iNom (trips at a short-circuit current of 75A)
|
Power consumption metering |
Separate power consumption metering on each managed channel |
Time of powering on managed channel |
Programmable (default delay 1 second) |
External indicator lights (display) |
Input state |
- On/Off/voltage and frequency params out of range alert (separately in phases)
- Grounding indication presence/absence
|
Сhannels (outlets) state |
On/Off/Short circuit/Output overcurrent/Input overcurrent |
Remote control and remote monitoring |
Input state |
- On/Off/voltage and frequency params out of range alert
- Current/Voltage/Frequency/Wattage
- Grounding indication presence/absence
|
Channels state |
- On/Off/Short circuit/Output overcurrent/Input overcurrent
- Managing current cutoff thresholds and power-on delay
|
Power consumption metering |
Separate power consumption metering on each of 30 managed channels |
Supported protocols |
- HTTP/HTTPS (WEB Interface/REST API)
- SSH
- SNMPv1, SNMPv2c, SNMPv3, SNMP Traps
- SMTP
- RADIUS
|
Automation (Watchdog) |
- Output channel (outlet) reset, if the miners hash rate decreases
- Output channel (outlet) reset, if there are no responses to ICMP requests (pings)
- Output channel (outlet) reset, if the TCP port is unavailable
- Output channel (outlet) reset, when the current decreases
|
Standards compliance |
Electromagnetic compatibility |
EAC (GOST30804 (IEC61000), GOST51317 (IEC61000)) |
Safety |
EAC (GOST51321 (IEC60439)) |
General parametres |
Communication interface |
3 х Ethernet 10/100 Mbps (one per each input) |
Accessories included |
Electric panel, wall mounting kit, quick install guide |
Panel size (width x height x depth) |
600х610х250 mm, wall mounting |
Module weight |
33.65 kg |
Operating temperature |
0 ~ +40 °С |
Storage temperature |
-20 ~ +60 °С |
Operating humidity |
45 ~ 85 % (no condensation) |
Cooling |
Passive |
Noise level |
Under 30 dBA (powering on/off and switching ports) |
Default Warranty |
1 year |